Quick Answer: What size breaker do I need for a 10hp motor?

Breaker size must be rated for a minimum of 125% of the full-load current of the motor it is protecting, rounded up to the next standard breaker size. For example, the full-load current of a 5 HP motor at 460V is 7.6 Amps. The breaker must be sized for 7.6 * 1.25 = 10 Amps .

What size breaker do I need for a 10 hp motor?

Full Load Current: Three Phase AC Motors

Motor Horsepower Size Breaker
5 230V 460V 15 15
7-1/2 230V 460V 40 30
10 230V 460V 50 30
15 230V 460V 70 40

How many amps does a 10 hp motor use?

AMP DRAW BASED ON HORSEPOWER

HP 1 Phase Amps 3 Phase Amps
115 volt 208 volt
5 56 16.7
7-1/2 80 24.2
10 100 30.8

How many amps does a 10hp single phase motor draw?

Full-Load Current in Amperes Single-Phase Alternating Current Motors

HP 115V 230V
5 56 28
7-1/2 80 40
10 100 50
The voltages listed are rated motor voltages. The listed currents are for system voltage ranges of 110 to 120 and 220 to 240.
IT IS INTERESTING:  How much does it cost to rebuild a classic car engine?

What size breaker do I need for a 5 hp motor?

A 5hp single phase AC motor has a load current of 28 Amps. So 10GA. wire with a 30 Amp breaker will work.

What size breaker do I need for a 1 hp motor?

How to Calculate How What Size Circuit Breaker a Machine will Need:

HorsePower of Main Motor 220 Volts, 1 phase 220 Volts, 3 phase
1 Hp 5.6 Amps 2.8
2 11.2 5.6
3 16.8 8.4
4 22.4 11.2

How do I convert HP to amps?

Converting horsepower to amps can be done in a few simple steps, or using this simple formula.

  1. Amps = (Horsepower × 746) ÷ Efficiency ÷ Volts.
  2. Watts = Horsepower × 746.
  3. Watts = Wattsη
  4. Amps = Watts ÷ Volts.
  5. Amps = HP × 746V × η × PF.

How many amps is a 40 hp motor?

AC Motor Full Load Amperes

HP 200 Volts 208 Volts
40 120 114
50 150 143
60 177 169
75 221 211

What size breaker do I need for a 7.5 hp motor?

You need 50 amp rated wire with a 50-100 amp breaker. 7.5hp=40 amps x 250%=100 amp breaker on #8 Thhn. If a 100amp breaker isn’t sufficient to start the motor without tripping I can then go up to a maximum of 400% of the motor rating.

How many amps does a 5 horsepower motor draw?

A 5 HP motor at 230V, 3PH is12.

Using the formula above, multiply 12.4 amps by 10% for a result of 1.24. Add this total to 12.4 for a total of 13.64 amps.

How much current would a 1.5 HP 240v motor draw?

The 1.5 HP Baldor motor that turns at 1725 will draw 18 amps according to its name plate.

IT IS INTERESTING:  Quick Answer: What is an iVCT engine?

What are the standard breaker sizes?

Standard sizes for fuses and fixed trip circuit breakers, per 240.6, are 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000 5000, and 6000 amps.

How do I know what size breaker I need?

To calculate the breaker size, simply divide the adjusted wattage by 240 volts to find the rated amperage needed for your subpanel. Often, the result is not a common circuit breaker size. and you can simply round up to the next higher size of ​the breaker.

Blog about car repair